Skip to main content

Early Detection of Weak Points in MEEC Distribution System

Research Abstract
paper is aimed at detecting the weak points in the distribution system of MEEC, "Middle Egypt Electricity Company". These include loose connections, polluted insulators and micro-roughness on line conductors and insulator hardware. The detection methodology is based on measuring ultrasound emissions from these weak points to warn against impending failures and subsequent supply interruptions. Laboratory testing made it possible to discriminate between loose-connection arcing, polluted-insulator "baby arcs" and sharp-edge corona according to the sound pattern. However, there can be occasions where sound pattern may prove confusing in discrimination between baby arcs and looseconnection arcing. In this case, recording of acoustic signals was found to be a useful tool for such discrimination.
Research Authors
M. Abdel-Salam, S Abdel-Sattar
Research Department
Research Journal
The 2001 IEEE / IAS Conference, Chicago, Illinois, USA, Sept. 30 - Oct. 4, 2001.
Research Member
Research Pages
2541-2545
Research Publisher
NULL
Research Rank
3
Research Vol
4
Research Website
NULL
Research Year
2001