Study Apparent Grounding Resistivity in Vertical-layer
Soil

ملخص البحث
Soil structure effects grounding systems designed to guarantee safe operation of electric power systems. This work investigated effects of the presence of two/three vertical adjacent mediums on measured apparent soil resistivity. The Wenner method was used to measure the apparent soil resistivity in the vertical-layer soil. Different vertical-layer soils were studied, such as two-verticallayer soil, three-parallel-vertical-layer soil, and three-perpendicularvertical- layer soil. Numerical models were used to model the four electrodes at different vertical-layer soil by using the current source simulation method. The measured apparent soil resistivities at different vertical-layer soils were compared with the apparent soil resistivity at a uniform-layer soil. Results show that the apparent soil resistivity was affected by the presence of vertical-layer/s soil. Different parameters affected the measured apparent soil resistivity, such as measuring angle slope with vertical layer, distance between measuring electrodes, and distance between measuring electrodes and interface between the vertical-layer soil.
مؤلف البحث
Mohamed Nayel
مجلة البحث
Electric Power Components and Systems
مؤلف البحث
صفحات البحث
845–851
تصنيف البحث
1
عدد البحث
VOL 42 NO.8
سنة البحث
2014