Skip to main content

Network reconfiguration in balanced distribution systems with variable load demand

Research Abstract
This paper presents a simple and efficient reconfiguration approach for balanced distribution networks with Distributed Generation (DG). The proposed approach starts with meshed networks by closing all tie switches. A switching index is defined for reconfiguration using apparent power flow in lines. The radial configuration was restored by opening the switch with the highest switching index in each loop subjected to system operational constraints. The time varying nature of loads through using daily load profiles in each node of the system was considered. The results concluded the effectiveness of the fixed configuration compared to hourly reconfiguration in terms of energy losses and number of switching operations. The proposed method has been tested on three systems with and without distributed generation, and compared with those reported in the literature.
Research Authors
Aboelsood Zidan and E. F. El-Saadany
Research Department
Research Journal
Recent Advances in Energy and Power Systems, RAEPS-12 conference
Research Member
Lect.
Research Rank
3
Research Website
http://www.icgst-amc.com/institute/Community.aspx?InstId=3&aid=3121
Research Year
2012